Section 17 -Output Device Programming
17–3
If a relay is energized before a 4-wire smoke detector is reset, the relay will be stopped by the
interruption of Aux.
Power that resets the smoke detector. If this is not desired, supply power to
the relay unit from another 12V power source (e.g., the same source that is powering external
equipment through the relay contacts).
Programming Output Relays and Powerline Carrier Devices
While in Program mode, press
80 to enter Output Device Menu mode. This mode is
used to program all output devices used in the system (Error! Bookmark not defined.4229
or Error! Bookmark not defined.4204 Relay Modules, or Powerline Carrier devices). Refer
to the Output Device Table for
80 in the separate “Programming Guide” form when
programming Output Devices.
NOTE: If you are using Powerline Carrier devices, the House ID of the devices must be
entered in data field
27.
After you key in
80, the following prompts are displayed.
Output Device Displays
Enter Device No.
(00 = Quit) 01
Enter the Device Number
01
or
02
for a 4229; or
01
,
02
,
03
, or
04
for a 4204; or
01
08
for Powerline Carrier devices; or
00
to end
these entries. Press
to continue.
The
key is used to accept an entry and advance to the next
prompt. The # key is used to revert back to the last question to
check or change an entry. Press
to go forward again.
02 A EV ZL ZT
STT 0 0 0 00
This screen displays a summary of the current Device START
programming (for this example, device 02 has been selected).
Press
to continue.
02 A EV ZL ZT
STP – – 0 00
This screen displays a summary of the current Device STOP
programming.
Press
to continue.
02 Device Action
No Response 0
Enter the desired device action as listed below. Press
to continue.
0 = No response 2 = Close and Stay Closed
1 = Close for 2 seconds 3 = Continuous Pulse on & off
(
1 sec ON,
1 sec OFF)
02 Start Event
Not Used 0
Enter the event to
start
the relay:
0 = Not used; 2 = Fault; 1 = Alarm; 3 = Trouble
A zone list must be used in conjunction with an event. If a zone
type/system operation is to be used instead of an event, enter
0
.
Press
to continue.
02 Start: Zn List
No List 0
If a zone list will be used to
start
the relay action, enter the zone
list number (to be programmed in field
81):
1
,
2
, or
3
. If not used,
enter
0
. Press
to continue.