Security Link SL150 Průvodce řešením problémů Strana 20

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 144
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 19
SL150 Installation and Setup Guide
3–2
The length of all wire runs must not exceed 1500 feet (457m) when unshielded quad conductor
cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on
the data lines when quad cable is used.
2. Run field wiring from the control to the keypads (using standard 4-conductor twisted wire
cable of the wire gauge determined in step 1).
3.
Connect
remote
keypads
to terminals 4, 5, 6, and 7 on the control board, as shown in
Figure 6.
KEYPAD
BLACK
RED
GREEN
YELLOW
4
5
6
7
CONTROL
TERMINALS
Figure 6. Keypad Connections to the Control Board
Mounting the Keypads
To mount the keypads, perform the following steps:
1. Make sure
all keypads
are set to the non-addressable mode (address 31), which is the
factory default setting. Refer to the instructions provided with the keypad for address
setting procedure.
2. Mount the keypads at a height that is convenient for the user. Refer to the instructions
provided with the keypad for mounting procedure.
You can either surface mount or flush mount keypads (using an appropriate Trim Ring
Kit:
6139TRK
). Refer to the mounting instructions and template included with the keypad
and/or trim ring kit for specific information.
Supplementary Power for Additional Keypads
The control provides 600mA (500mA max for UL) for powering keypads (up to 8) and other
devices from the auxiliary power output. The backup battery will supply power to these
keypads in the event that AC power is lost.
When the
control’s
auxiliary power load for all devices exceeds 600 mA (500mA max for UL),
you can power additional keypads from a regulated 12VDC Power Supply (e.g.,
487-12
supplies 12V, 250mA;
488-12
supplies 12V, 500mA). Use a
UL
Listed, battery-backed supply
for UL installations.
The 487–12/488–12
power
supplies contain a backup battery that can power these keypads in
the event of AC power loss to the main supply.
Keypads powered from supplies that do not have a backup battery
will not function
when AC
power is lost. Therefore, be sure to power at least one keypad from the control's auxiliary power
output.
Connect the additional keypads as shown in
Figure 7
, using the keypad wire colors shown. Be
sure to observe the current ratings for the power supply used.
Zobrazit stránku 19